Reduction in Harmonics in Marble Industry

Prakash sundaram1, Shimi S.L.2, Dr.S.Chatterji3
Professor and Head, Department of Electrical Engineering, Vidya bhawan polytechnic college, Udaipur, Rajasthan, India1
Assistant Professor, Department of Electrical Engineering, NITTTR, Chandigarh, India2
Professor and Head, Department of Electrical Engineering, NITTTR, Chandigarh, India3
Related article at Pubmed, Scholar Google

Visit for more related articles at International Journal of Innovative Research in Science, Engineering and Technology

Abstract

Lower order harmonic are major problems in industries in India. This will get worse due to the increasing number of lagging power factor induction motors and harmonic generated non linear loads. During survey of Udaipur, Rajasthan (India) investigator found the poor condition of power quality in large number of marble, soft stone and minerals industries and took one marble industry for investigation of the power quality due to harmonic content in power supply. After measurement in Arihant Marble industry, Udaipur, Rajasthan (India), the investigator found that the 5th harmonic content was beyond the IEEE limits. Investigator then design the harmonic filter at Hercules Controls Panel Pvt. Ltd. Udaipur, Rajasthan (India), after installation of harmonic filter at Arihant Marble Industry and measurement were done again and found that 5th harmonic content was below IEEE limits. Investigator also calculate the kVA saving.

Keywords

Harmonic Reduction, Passive Harmonic Filter, Marble / Soft stone Industry

INTRODUCTION

Highest power tariffs is paid by Indian industry in the world and the gap between supply and demand is expanding leading to poor quality and lower quantity of power resulting in loss of production and profits[2]. Unfortunately, in India, there is very less awareness of low power factor and harmonic pollution and the available solutions to curtail down it. “Poor power factor” was considered as the only parameter to measure the efficiency of electrical system in earlier days and hence, traditionally, more emphasis was given on the solutions to improve the power factor. The incentive schemes and imposition of penalty for maintaining the PF by Electricity Board’s has drawn user’s attention toward the PF improvement. But only PF improvement does not compete the challenge posed by high percentage of harmonics getting injected into the supply. Thus there is large need of energy saving in electrical systems i.e. there is need to improve system power quality for several different benefits like reducing peak kW billing demand ,increased system capacity, reduced system losses in electrical system, increased voltage level in electrical system and cooler, more efficient motors.
Harmonic: Power quality has caused a great concern to electrical system with the increasing use of sensitive and susceptive electronic and computing equipments and all nonlinear loads. The results are generation of harmonics. High level of harmonic distortion can create stress and resultant problems for the utility's distribution system, the plant's distribution system, as well as the plants equipments. .In electrical engineering harmonics are described as follows as per IEEE 1159- 1995.[4]
The Total Harmonic Distortion (THD) is a measure of the effective value of harmonic distortion
image
Where: THD is the total harmonic distortion of the waveform in %,
I1 is the magnitude of the fundamental component and
I2, I3, I4 is the magnitude of the 2nd, 3rd 4th harmonic components.
Marble and soft stone industries are the largest consumers of electricity (approximately 60%) of the total industrial consumption of electricity of Udaipur, Rajasthan (India). Marble and soft stone industry has very poor power factor (0.4 to 0 .8) and they were penalized for that by Rajasthan State Electricity Board along with poor quality of power. Recently some industries used manually operated capacitor banks which are not effective and sufficient. Also a marble and soft stone industry uses non linear loads and various electronics loads which further degraded the quality of power supply by harmonic generation. That is why harmonic reduction is required.

II. ENERGY SAVING TECHNIQUES

In the areas for improvement in electrical systems resulting in energy conservation/saving are:
(i) Power factor management
(ii) Demand side management.
(iii) Improvement in quality of power (Reduction in harmonics).

III. METHODS FOR REDUCTION OF HARMONIC DISTORTION

One of the ways to resolve the issue of harmonics would be using filters in the power system. Installing a filter for nonlinear loads connected in power system would help in reducing the harmonic effect. With the increase of nonlinear loads in the power system, more and more filters are required. There are two types of filters (i) Passive Filters (ii) Active Filters.[6] [12] Inductors and Capacitors are commonly used in the active and passive filters for harmonics reduction. The passive filters are used in order to protect the power system by restricting the harmonic current to enter the power system by providing a low impedance path. Passive filters consist of resistors, inductors and capacitors. The active filters are mostly used in distribution networks for elimination/reduction of problem like sagging in voltage and flickering, where there are harmonics in current and voltages, etc. There is also a third type of filter which is used i.e. the hybrid filter. Hybrid filters are composed of the passive and active filters both. [2]

IV. DESIGN OF A PASSIVE HARMONIC FILTER (PHF)

A harmonic filter essentially consists of a power capacitor, a tuning reactor and its control gear. It will act in parallel with an untuned basic power factor improvement capacitor bank. For the designing purpose investigator collected some datas such as load details, existing power factor, required new power factor, total harmonic distortion, individual harmonic details etc. This data can be obtained from a harmonic analyzer.
Harmonic Filter Design
Step-A: Investigator measured the electrical data of Arihant Marble with the help of energy meter and harmonic analyzer as follows:
a) Energy meter data:
Data was measured from the energy meter installed at Arihant Marble Pvt. LTD. Udaipur. From table 1 the maximum demand in HP = 57Hp, the maximum demand in kW = 53.15 kW, and Maximum load current =119.26 A.Design of harmonic filter is done at 30% of the load (kW)
Load in kW = 30% of 53.15 kW =16 kW
Lowest Power factor measured = 0.60 lag
b) Data obtained from Harmonic Analyzer at 30% load:
Total harmonic current in power supply system THD = 5.6 A
5th harmonic current = 8.0 A----------------------------- (3)
During measurement investigators found that only 5th order harmonic was beyond the limit of harmonic and other orders were under limits.
Step-B Assuming required power factor to be 0.99, calculate the total kVAR required to raise the power factor from 0.60 to 0.99.
kVAR required = kW (tan Ø1-tan Ø2) ---------------------- (4)
Lowest power factor CosØ 1 = 0.60 tan Ø1 = 1.333
Required power factor CosØ 2 = 0.99 tanØ 2 = 0.142
kVAR required = 16 (1.333 - 0.142) = 20 kVAR.
Thus 20 kVAR capacitor required to raise the power factor to 0.99. It can be seen that, ITHD is 5.6 but maximum harmonic current distortion as recommended by IEEE specifications C-519-1992 is = 4.0.
Out of 20 kVAR calculated from equation (4) to be installed we employ 30% kVAR towards filter duty and remaining kVAR for power factor correction. (Thumb rule).
Filter kVAR= 30% of 20 kVAR = 6 kVAR.
Step-C Design of filter: Investigators decided to design passive shunt harmonic filter. A 3-phase passive filter consists of 3 reactors and 3 capacitors in which capacitors are connected in star. Investigators have to calculate the reactor and capacitor value in mH/phase and μF/phase and also in kVAR value. For designing of reactor, investigator calculates the condition of resonance. Since investigator found during measurement of harmonic content, 5th harmonic level beyond the IEEE standard. Thus calculation of capacitive reactance at 5th harmonic frequency (5x50=250Hz) at resonance was done.
Inductive Reactance at 50Hz XC50 = 1/2πfC = 1/2π x 50 x C
Inductive Reactance at 250Hz XC250 = 1/2πfC = 1/2π x 250 x C
Using above two relation
XC250 = XC50/ 5 ------------------------------------- (5)
For XC250, first investigators calculated the capacitive reactance at 50Hz where
XC50 =1/2πfC ----------------------------------------- (6)
Step-1 Capacitance per phase: For above relation capacitor value in μF/phase is required thus investigators using the following relation
kVAR per phase = (kV2 x 2πfC x 10-3)
C = kVAR per phase/ (kV2 x 2πf x 10-3) ------------ (7)
Where kVAR per phase = kVAR for 3-phase/ No. of phase = 6/3 = 2kVAR
kVph = kVline/√3= 0.415/1.732 = 0.230 kV
Capacitor C becomes using equation (7)
C = 2/ (0.2309)2 x 2 x 3.14 x 50 x 10-3 = 111.50 μF /Ph.
Step-2 capacitive reactance at 50Hz: capacitor value obtained in step-1, calculated the capacitive reactance at 50Hz frequency using equation (6)
XC50 = 1/ (2x3.14x50 x 111.50 x 10-6) = 28.562Ω/Ph.
Step-3 capacitive reactance at 250Hz: Since only 5th order harmonic are beyond the limits of harmonic thus investigators calculated the capacitive reactance at 250Hz (5 X 50Hz) using equation (5)
XC250 =XC50/ 5 = 28.562 /5= 5.712 Ω /Ph.
Step-4 Calculation of inductor: For resonance at 5th harmonic we should have,
XL250 = XC250 --------------------------------------------- (8)
XL250 = 5.712 Ω /Ph.
Investigators calculated the inductive reactance at 50Hz using following relation
XL50 =XL250/5 = 5.712/5= 1.142 Ω /Ph. ---------------- (9)
From equation (9) inductive reactance at 50Hz, calculated the value of inductance from following relation by putting the value of inductance obtained in step- 4.
XL50 = 2πf L
L = XL50/2π=1.142/314 =3.6mH----------------------- (10)
After calculated the values of inductor, Investigators calculated the values of inductor in terms of kVAR.
Step-5 kVAR rating of Reactor: kVAR of inductor calculated by following relation
kVAR =VL x IRMS--------------------------------------- (11)
Where VL = Voltage across reactor and given by relation
VL=VL50 + VL250-------------------------------------------- (12) and
IRMS= Resultant rms current due to fundamental and 5th order harmonics and given by following relation
IRMS = [I50) ²+ (I250) ²]½ ------------------------------------ (13)
(a) VL50 = Voltage drop across reactor due to fundamental Current and is given by following relations
VL50 = IC50 x XL50---------------------------------- (14)
Where IC50 = Capacitor current at 50 Hz and is calculated by following expression
IC50 = kVAR/ (1.732 x line voltage) ----------------------- (15)
= 20/ (1.732 x 0.415) = 27.82 Amp
Putting the value of IC50 from equation (15) and value of XL50 from equation (9) in equation (14)
VL50 = I50 x XL50
= 27.82 x 1.142 = 31.77 V. -------------------------- (16)
(b) VL250 = Voltage drop across reactor due to 5th harmonic current and is obtained by relation
VL250 = I250 x XL250 ----------------------------------------- (17)
Where I250 = current at 250Hz and XL250 is Inductive reactance at 250Hz. Putting the value of I250 from equation (3) and value of XL 250 from equation (8) in equation (17)
VL250 = 8.0 x 5.712 = 45.696V. ------------------------- (18)
Putting the value of VL50 from equation (16) and value of VL250 from equation (18) in equation (12)
VL= VL50 + VL250
= 31.77+45.69 = 77.466 Say 78 V. ------------- (19)
(c) RMS current:- For calculating the resultant rms current due to fundamental and 5th order harmonic, putting the value of current at 50Hz from equation (15) and value of current at 250Hz = 8 Amp from equation (3) in equation (13)
IRMS= [(27.82) ² + (8) ² ] ½ = 28.94Amp. ------------------- (20)
kVAR rating of Reactor: For kVAR rating of reactor, putting the values of VL from equation (19) and values of IRMS from equation (20) in equation (11)
kVAR = VL x IRMS = 78 x 28.96
= 2243.41 VAR/Ph. = 2.243kVAR/Ph ------------------ (21)
kVAR rating of capacitor. As per maximum demand of plant, investigator found the total value of capacitor was 20 kVAR. Out of 20 kVAR, 6 kVAR were used in filter and remaining was used in P.F correction. Thus 6kVAR was used for 3 phase i.e 2 kVAR/phase was used in harmonic filter. The voltage rating of capacitor was calculated as follows.
VC = VC50 + VC250 ----------------------------------------- (22)
Where VC50 (Phase) = Line voltage/√3
= 415/1.732= 239.6 V. ------------ (23)
VC250 = I250 x XC250
= 8 X 5.712. (From equation (3) and step 3)
= 45.696V. ------------------------------------------- (24)
Total voltage across capacitor VC = VC50+ VC250
= 239.6+45.696 (From equation (23) and (24)
= 285.296 V (ph voltage) = 494.13 V (line voltage) = 500 V
After designing the harmonic filter, the fabrication of the harmonic filter has been done at Hercules panel Pvt. Ltd. Udaipur (India).

V. INSTALLATION OF HARMONIC FILTER AND MEASUREMENT

During the measurement of harmonic content in supply system using harmonic analyzer, investigator found that only 5th order of harmonic is beyond the limit of harmonic as per IEEE specifications C-519-1992 and limit is 4%. To reduce the 5th harmonic content, above 5th order harmonic filter was installed and again measurement was done by harmonic analyzer. Investigator tabulated all lower order harmonic values with and without filter shown in Table 4 and graphically in fig.I
VI. RESULTS OF HARMONIC MEASUREMENT
The following observations were made:
(1) Input current reduced from 52 to 44 A / Ph
(2) kVA demand reduced from 50.51 to 43.18
(3) Input PF is improved from 0.79 to 0.85
(4) 5th harmonic level is reduced from 7.1% THD to 3.5% THD

VII. CONCLUSION

From installation of harmonic filter at Arihant Marble Industry following conclusions were made:
(1) The 5th harmonic component was found 3.5%.
(2) The line current and the line losses were reduced and heating of cables were avoided.
(3) Harmonic filter improved the supply voltage waveform
(4) The overall efficiency of the plant increases and overall maintenance cost of plant reduces.
(5) Noise, EMI and RFI in the plant are eliminated.
(6) Generator and transformer heating issues were resolve.

Tables at a glance

Table icon
Table 1
 

Figures at a glance

Figure 1
Figure 1
 

References

  1. Walter T.J. Hulshorst, Keet L. and John Enslin E.R., “Harmonic Analysis and Mitigation in Large Industrial Steel lants” Electrical Power Quality and Utilization Magazine, Vol. 11, pp 57-63, 2006.
  2. Khatavkar V.V., Chapbekar S.N., “Study of Harmonics in Industries - Power Quality Aspect”, Electrical India Magzines, Vol. 46, pp 188-192, 2006.
  3. Aware M.V., Kothari A.G. and Bhatt S.S., “Power Factor Improvement Using Active Filter for Unbalanced Three-Phase Non-Linear Loads” International Journal on Energy Technology and Policy, Vol. 4, pp 103-117, 2006.
  4. Ashish Pandey, Kothari D.P. and Bhatt S.S., “Power Quality Issues and Power Electronics” International Journal Energy Technology and Policy, Vol. 4, pp 4-18, 2006.
  5. Escobar, G., Stankovic, Cardenas A.M., Mattavelli V.P., “An Adaptive Controller for a Series Active Filter to Compensate Voltage Sags, Unbalance and Harmonic Distortion”, Proceedings of VIII IEEE Technical Proceedings, pp. 275 - 280, 20-24, 2002.
  6. António P. Martins, “The Use of an Active Power Filter for Harmonic Elimination and Power Quality Improvement in A Nonlinear Electrical Installation”. IEEE Transactions on Industrial Electronics, pp 1-5, 2000.
  7. Sharmeela C., Mohan M.R., Uma.G and Baskaran J., “Fuzzy Logic Controller Based Three-phase Shunt Active Filter for Line Harmonics Reduction” Journal of Computer Science Publications, pp 76-80, 2007.
  8. Elham B. Makram, Kasikci, “Harmonics and Quality of Power” Proceedings of Ninth International Conference, IEEE, Vol.3, pp 810 - 815, 2000.
  9. Akagi H., “Modern Active Filters and Traditional Passive Filters” Bulletin of the Polish Academy of Sciences, Technical Sciences, Vol. 54, pp 255- 269, 2006.
  10. Jonathan K. Piel, Daniel J. Carnovale, “Economic and Electrical BenefitsOf Harmonic Reduction Methods in Commercial Facilities” Proceedings of 13-International Conference, IEEE, pp 81- 89, July 2004.
  11. Moinuddin K Syed, Sanker Ram B.V., “A Fuzzy Logic Model for Harmonic Reduction in Three Phase Shunt Active Filter” Proceedings of International Journal of Electronic Engineering Research, Vol. 2, pp 357–364, 2010.
  12. Bhonsle D.C., Kelkar R.B., Zaveri N.K., “Power Quality Improvement: Harmonic Measurement and Simulation”, 23rd National Convention of Electrical Engineers, Pune, pp 108-111, 2007.