Keywords
|
Reactive Power Compensation, Voltage Source Converter (VSC), STATCOM, GTO, SHEM, Phase Locked Loop (PLL), Multilevel Inverter, THD, SPWM. |
INTRODUCTION
|
In a long transmission lines due to unbalanced and non linear loads there is a considerable transmission losses. These transmission losses will give rise to power quality issues in electrical power system. Due to sensitive loads present at the consumer side and deregulated market issues, it is necessary to provide quality power to the consumers. In order to meet all power quality problems like voltage sags, voltage swells, we are placing many fact devices like synchronous condenser, static VAR compensator, static synchronous compensator. So the performance of the ac system can improve by all these fact devices. |
Among all these STATCOM is the one which having better reactive power compensation capability and better control over voltage. In STATCOM there is a GTO or IGBT based 3 phase voltage source inverter, step down transformer and a DC capacitor. FACTS technology is the most advanced and most effective technology in which better voltage control, reactive power flow control, steady state stability, transient stability is possible. It can minimize the operational cost, which leads to reduced per unit cost. |
STATCOM STRUCTURE AND PRINCIPLE OF OPERATION
|
The STATCOM basically consists of a step down transformer with a leakage reactance, a voltage source inverter (VSI), a capacitor in its DC side and a control system. The inverter in conventional STATCOM, switched with a single pulse per period and the transformer is connected in order to provide harmonic minimization and serve as a link between VSI and the system. For purely reactive power flow the three phase Voltages of the STATCOM must be maintained in phase with the system voltages. The variation of reactive power is performed by means of a VSC connected through a coupling transformer. |
The VSC uses forced commutated power electronics devices (GTO's or IGBT's) to synthesize the voltage from a dc voltage source. The operating principle of STATACOM is explained in Fig.1. It can be seen that if ïÿýïÿýïÿýïÿý > ïÿýïÿýïÿýïÿý then the reactive current Iq flows from the converter to the ac system through the coupling transformer by injecting reactive power to the ac system. On the other hand, if ïÿýïÿýïÿýïÿý > ïÿýïÿýïÿýïÿýthen current Iq flows from ac system to the converter by absorbing reactive power from the system. Finally, if ïÿýïÿýïÿýïÿý = ïÿýïÿýïÿýïÿý then there is no exchange of reactive power. The amount of reactive power and real power exchange is given by: |
|
Where, |
ïÿýïÿýïÿýïÿý: Magnitude of system Voltage. |
ïÿýïÿýïÿýïÿý: Magnitude of STATCOM output voltage. |
ïÿýïÿý: Equivalent impedance between STATCOM and the system. |
CASCADED NINE LEVELS H BRIDGE INVERTER
|
A cascaded multi level inverter consists of series H-bridge inverter units. The general function of this multi level inverter is to synthesize a desired voltage from several DC sources, which may be obtained from batteries, fuel cells, or solar cells. Each SDCS is connected to an H-bridge inverter. |
The ac terminal voltage of different level inverters are connected i9n series. The amplitude of the odd harmonic order of the output voltage with 2N+1 level can be represented using Fourier's series method as, |
Where |
|
ïÿýïÿýïÿýïÿý is the amplitude of voltage harmonic of nth order |
ïÿýïÿýïÿýïÿýïÿýïÿý is the DC voltage across the capacitor |
N is the number of the bridges in each phase n is the odd harmonic order |
ïÿýïÿýïÿýïÿý is the switching angle of the single phase bridge In this paper a nine level cascaded multilevel converter is designe and is simulated in MA TLAB simulink environment.d |
The firing angles of the bridges in the converter are so chosen such that 5th, 7th, l1th and13th harmonics are eliminated and the THD of phase voltage is minimized. For the optimal values of firing angles the following equations must be solved (considering the modulation index M = 1) |
|
|
This set of nonlinear transcendental equations can be solved by iterative methods such as the Newton-Raphson method. We get, |
|
The 9 level PWM (pulse width modulation) converter is implemented in MATLAB simulink and respective output voltage waveform is shown in Fig 4. |
CONTOL STRATEGY FOR STATCOM (STATCOM CONTROLLER)
|
The main objective for control of STATCOM is to enhance the power transmission by injecting or absorbing reactive power to or from the grid. The basic control strategy used for the proposed STA TCOM controller is direct control. In this approach reactive output current can be controlled directly by the internal voltage control mechanism of the converter in which the internal dc voltage is kept constant. The STATCOM is controlled to deliver either inductive or capacitive currents to the power system by varying its output voltages V2a, V2b and V2e. In the design of the STATCOM controller, the three-phase quantities are first transformed into direct and quadrature components in a synchronously rotating reference frame. Then, a current regulator is employed for the current control. |
In addition, an ac voltage controller is designed to regulate the PCC bus voltage through a PI controller. The ac voltage controller generates the desired reactive current reference for the current regulator. In the design of the STATCOM controller, it is essential to have good dynamic response in the transient period and to ensure minimal harmonics at steady state. As shown in Fig. 5, a transient modulation-index controller and steady-state modulation-index regulator are proposed to achieve the goals of good transient response and minimal steady-state harmonics respectively. Details for the design of transient modulation index controller, steady-state modulation-index regulator, phase locked loop (PLL), abc to dqo transformation, AC voltage controller, Current regulator, PWM generator are discussed in this paper |
IMPLEMENTATION AND RESULTS
|
A basic power system model is designed consisting of 3-phase source of 100MVA and a line voltage of llkV. At the load centre various loads are considered and are connected to system at different instants of time as shown in the Table |
Fig. 6 depicts the load voltage and current waveforms of the power system without STATCOM. In the interval 0.3s to O.4s there is a dip in the voltage level due to inductive load and from 0.5s to 0.6s there is a rise in the voltage level due to capacitive loaded conditions, but such voltage fluctuations are not desirable for a power system. |
Hence the 9 level STATCOM and its controller is connected to the power system as shown in Fig.7 and the corresponding load voltage and current waveforms are shown in Fig. 8. The voltage waveform in the Fig.8 is maintained constant throughout indicating constant load voltage irrespective of the load connected and thereby improving voltage profile of the system. |
Hence the 9 level STATCOM and its controller is connected to the power system as shown in Fig.7 and the corresponding load voltage and current waveforms are shown in Fig. 8. The voltage waveform in the Fig.8 is maintained constant throughout indicating constant load voltage irrespective of the load connected and thereby improving voltage profile of the system. |
For analyzing the quality of the voltage waveform total harmonic distortion calculations are performed using equation |
|
The THD of output voltage is calculated and is found to be l.77% as shown in the Fig. 9 and the same is compared with the THD of various papers as shown in Table.2 and is found to be minimum. |
CONCLUSION
|
The paper presents a STATCOM model, developed with the necessary components and controllers in order to demonstrate its effectiveness in maintaining simple and fast voltage regulation at any point in the transmission line. On the other hand, the harmonics generated by the ST ATCOM is kept minimal with the implementation of SHEM. The effectiveness of the proposed control strategy is demonstrated with the help of THD calculations and is found to be minimum when compared with various designs. Hence the proposed S TATCOM with it controller employing the direct control strategy is able to maintain the voltage balance under various load conditions. |
Tables at a glance
|
|
|
Table 1 |
Table 2 |
|
|
Figures at a glance
|
|
|
|
|
|
Figure 1 |
Figure 2 |
Figure 3 |
Figure 4 |
Figure 5 |
|
|
|
|
|
Figure 6 |
Figure 7 |
Figure 8 |
Figure 9 |
Figure 9b |
|
|
References
|
- Ben-Sheng Chen and Yuan-Yih Hsu," An Analytical Approach to Harmonic Analysis and Controller Design of a STATCOM", IEEE Trans. Power Delivery, Vol. 22, No. I, Jan 2007.
- T. Manokaran, B.Sakthivel and Mohamed Yousuf,"Cascaded Multilevel Inverter Based Harmonic Reduction in Statcom" International Journal of Engineering Science and Technology, Vol. 2(10), 20 10.
- R.S. Dhekekar and N.V. Srikanth,"H-Bridge Cascade Multilevel VSC Control for Effective V AR Compensation of Transmission Line" 16th National Power Systems Conference, December, 20 10.
- K. VenkataSrinivas, Bhim Singh, Ambrish Chandra and Kamal-AIHaddad,"New Control Strategy Of Two-Level 12-Pulse Vsc Based Statcom Using Hybrid Fuzzy-Pi Controller" Indian Institute of Technology Delhi.
- NitusVoraphonpiput, TeratamBunyagul, and SomchaiChatratana, "Analysis and Performance Investigation of a Cascaded Multilevel STATCOM for Power System Voltage Regulation".
- ChunyanZang, Zhenjiang Pei, Junjia He, Guo Ting, Jing Zhu and Wei Sun, "Comparison and Analysis on Common Modulation Strategies for the Cascaded Multilevel ST A TCOM" PEDS2009.
- Carlos A.c. Cavaliere, Edson H. Watanabe and Mauricio Aredes, "Analysis and Operation of STAT COM in Unbalanced Systems".
- Naveen Goel, R.N. Patel and Saji T. Chacko, "Genetically Tuned STATCOM for Voltage Control and Reactive Power Compensation", International Journal of Computer Theory and Engineering, Vol. 2, No. 3, June, 20 10.
- Amir H. Norouzi and A. M. Sharaf, 'Two Control Schemes to Enhance the Dynamic Performance of the STATCOM and SSSC", IEEE Trans. BOn Power Delivery, Vol. 20, No. 1, Jan 2005.
- Hung-Chi Tsai, Chia-Chi Chu and Sheng-Hui Lee, "Passivity-based Nonlinear STATCOM Controller Design for Improving Transient Stabilityof Power Systems", 2005 IEEE/PES Transmission and Distribution Conference & Exhibition: Asia and Pacific Dalian, China.
|
BOOKS
|
- N.G.Hingorani,L.Gyugyi, Understanding FACTS, Concepts and Technology of Flexible AC Transmission systems, IEEE Press 2000.
- K.R.Padiyar, FACTS Controllers in power Transmission
|